6-12 489 Generator Management Relay GE Multilin
6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS
6
0306 INPUT G PICKUP 0 to 4 1 F123 0
0307 TACHOMETER PICKUP 0 to 4 1 F123 0
0308 OVERCURRENT PICKUP 0 to 4 1 F123 0
0309 NEG SEQ OVERCURRENT PICKUP 0 to 4 1 F123 0
030A GROUND OVERCURRENT PICKUP 0 to 4 1 F123 0
030B UNDERVOLTAGE PICKUP 0 to 4 1 F123 0
030C OVERVOLTAGE PICKUP 0 to 4 1 F123 0
030D VOLTS/HERTZ PICKUP 0 to 4 1 F123 0
030E UNDERFREQUENCY PICKUP 0 to 4 1 F123 0
030F OVERFREQUENCY PICKUP 0 to 4 1 F123 0
0310 NEUTRAL O/V (FUND) PICKUP 0 to 4 1 F123 0
0311 NEUTRAL U/V (3rd) PICKUP 0 to 4 1 F123 0
0312 REACTIVE POWER PICKUP 0 to 4 1 F123 0
0313 REVERSE POWER PICKUP 0 to 4 1 F123 0
0314 LOW FORWARD POWER PICKUP 0 to 4 1 F123 0
0315 RTD #1 PICKUP 0 to 4 1 F123 0
0316 RTD #2 PICKUP 0 to 4 1 F123 0
0317 RTD #3 PICKUP 0 to 4 1 F123 0
0318 RTD #4 PICKUP 0 to 4 1 F123 0
0319 RTD #5 PICKUP 0 to 4 1 F123 0
031A RTD #6 PICKUP 0 to 4 1 F123 0
031B RTD #7 PICKUP 0 to 4 1 F123 0
031C RTD #8 PICKUP 0 to 4 1 F123 0
031D RTD #9 PICKUP 0 to 4 1 F123 0
031E RTD #10 PICKUP 0 to 4 1 F123 0
031F RTD #11 PICKUP 0 to 4 1 F123 0
0320 RTD #12 PICKUP 0 to 4 1 F123 0
0321 OPEN SENSOR PICKUP 0 to 4 1 F123 0
0322 SHORT/LOW TEMP PICKUP 0 to 4 1 F123 0
0323 THERMAL MODEL PICKUP 0 to 4 1 F123 0
0324 TRIP COUNTER PICKUP 0 to 4 1 F123 0
0325 BREAKER FAILURE PICKUP 0 to 4 1 F123 0
0326 TRIP COIL MONITOR PICKUP 0 to 4 1 F123 0
0327 VT FUSE FAILURE PICKUP 0 to 4 1 F123 0
0328 CURRENT DEMAND PICKUP 0 to 4 1 F123 0
0329 MW DEMAND PICKUP 0 to 4 1 F123 0
032A Mvar DEMAND PICKUP 0 to 4 1 F123 0
032B MVA DEMAND PICKUP 0 to 4 1 F123 0
032C ANALOG INPUT 1 PICKUP 0 to 4 1 F123 0
032D ANALOG INPUT 2 PICKUP 0 to 4 1 F123 0
032E ANALOG INPUT 3 PICKUP 0 to 4 1 F123 0
032F ANALOG INPUT 4 PICKUP 0 to 4 1 F123 0
0330 NOT PROGRAMMED PICKUP 0 to 4 1 F123 0
0331 SIMULATION MODE PICKUP 0 to 4 1 F123 0
0332 OUTPUT RELAYS FORCED PICKUP 0 to 4 1 F123 0
0333 ANALOG OUTPUT FORCED PICKUP 0 to 4 1 F123 0
0334 TEST SWITCH SHORTED PICKUP 0 to 4 1 F123 0
0335 GROUND DIRECTIONAL PICKUP 0 to 4 1 F123 0
0336 IRIG-B ALARM PICKUP 0 to 4 1 F123 0
0337 GENERATOR RUNNING HOUR PICKUP 0 to 4 1 F123 0
STATUS / DIGITAL INPUTS
0380 ACCESS SWITCH STATE 0 to 1 1 F207 0
0381 BREAKER STATUS SWITCH STATE 0 to 1 1 F207 0
0382 ASSIGNABLE DIGITAL INPUT1 STATE 0 to 1 1 F207 0
0383 ASSIGNABLE DIGITAL INPUT2 STATE 0 to 1 1 F207 0
0384 ASSIGNABLE DIGITAL INPUT3 STATE 0 to 1 1 F207 0
0385 ASSIGNABLE DIGITAL INPUT4 STATE 0 to 1 1 F207 0
0386 ASSIGNABLE DIGITAL INPUT5 STATE 0 to 1 1 F207 0
0387 ASSIGNABLE DIGITAL INPUT6 STATE 0 to 1 1 F207 0
0388 ASSIGNABLE DIGITAL INPUT7 STATE 0 to 1 1 F207 0
0389 TRIP COIL SUPERVISION 0 to 1 1 F132 0
STATUS / REAL TIME CLOCK
03FC DATE (READ-ONLY) N/A N/A N/A F18 N/A
03FE TIME (READ-ONLY) N/A N/A N/A F19 N/A
METERING DATA / CURRENT METERING
0400 PHASE A OUTPUT CURRENT 0 to 999999 1 Amps F12 0
Table 6–1: 489 MEMORY MAP (SHEET 3 OF 24)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–33
Page view 173