4-80 489 Generator Management Relay GE Multilin
4.13 S12 TESTING 4 SETPOINTS
4
4.13.3 FAULT SETUP
PATH: SETPOINTS ÖØ S12 TESTING ÖØ FAULT SETUP
The values entered here are substituted for the measured values in the 489 when the SIMULATION MODE is "Simulate Fault".
FAULT SETUP
[ENTER] for more
FAULT Iphase
OUTPUT: 0.00 x CT
Range: 0.00 to 20.00 × CT in steps of 0.01
FAULT VOLTAGES
PHASE-N: 1.00 x Rated
Range: 0.00 to 1.50 × Rated in steps of 0.01
Entered as a phase-to-neutral quantity.
FAULT CURRENT
LAGS VOLTAGE:
Range: 0 to 359° in steps of 1
FAULT Iphase
NEUTRAL: 0.00 x CT
Range: 0.00 to 20.00 × CT in steps of 0.01
180° phase shift with respect to Iphase OUTPUT
FAULT CURRENT
GROUND: 0.00 x CT
Range: 0.00 to 20.00 × CT in steps of 0.01
CT is either XXX:1 or 50:0.025
FAULT VOLTAGE
NEUTRAL: 0 Vsec
Range: 0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in secondary volts
FAULT STATOR
RTD TEMP: 40°C
Range: 50 to 250°C in steps of 1
FAULT BEARING
RTD TEMP: 40°C
Range: 50 to 250°C in steps of 1
FAULT OTHER
RTD TEMP: 40°C
Range: 50 to 250°C in steps of 1
FAULT AMBIENT
RTD TEMP: 40°C
Range: 50 to 250°C in steps of 1
FAULT SYSTEM
FREQUENCY: 60.0 Hz
Range: 5.0 to 90.0 Hz in steps of 0.1
FAULT ANALOG
INPUT 1: 0%
Range: 0 to 100% in steps of 1
FAULT ANALOG
INPUT 2: 0%
Range: 0 to 100% in steps of 1
FAULT ANALOG
INPUT 3: 0%
Range: 0 to 100% in steps of 1
FAULT ANALOG
INPUT 4: 0%
Range: 0 to 100% in steps of 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Page view 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 258 259

Comments to this Manuals

No comments