5-24 489 Generator Management Relay GE Multilin
5.6 A5 EVENT RECORDER 5 ACTUAL VALUES
5
The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event
is stored and a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for
troubleshooting. Events include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which
always records as events), loss of control power, application of control power, thermal resets, simulation, serial communica-
tion starts/stops and general input control functions optionally.
EVENT01 is the most recent event and EVENT40 is the oldest event. Each new event bumps the other event records down
until the 40th event is reached. The 40th event record is lost when the next event occurs. This information can be cleared
using S1 489 SETUP ÖØ CLEAR DATA ÖØ CLEAR EVENT RECORD setpoint. The event record will not update if a digital input
programmed as Test Input is shorted.
ANALOG INPUT 2
EVENT01: 0.0 Units
Range: 50000 to 50000
Seen only if the Analog Input is in use.
ANALOG INPUT 3
EVENT01: 0.0 Units
Range: 50000 to 50000
Seen only if the Analog Input is in use.
ANALOG INPUT 4
EVENT01: 0.0 Units
Range: 50000 to 50000
Seen only if the Analog Input is in use.
Table 5–1: CAUSE OF EVENTS
TRIPS
Ambient RTD12 Trip * Analog I/P 1 to 4 Trip * Bearing RTD 7 Trip * Bearing RTD 8 Trip *
Bearing RTD 9 Trip * Bearing RTD 10 Trip * Differential Trip Distance Zone 1 Trip
Distance Zone 2 Trip Field-Bkr Discr. Trip Gnd Directional Trip Ground O/C Trip
Hiset Phase O/C Trip Input A to G Trip * Loss of Excitation 1 Loss of Excitation 2
Low Fwd Power Trip Neg Seq O/C Trip Neutral O/V Trip Neut. U/V (3rd) Trip
Offline O/C Trip Overfrequency Trip Overvoltage Trip Phase O/C Trip
Phase Reversal Trip Reactive Power Trip Reverse Power Trip RTD11 Trip *
Sequential Trip Stator RTD 1 Trip * Stator RTD 2 Trip * Stator RTD 3 Trip *
Stator RTD 4 Trip * Stator RTD 5 Trip * Stator RTD 6 Trip * Tachometer Trip
Thermal Model Trip Underfrequency Trip Undervoltage Trip Volts/Hertz Trip
ALARMS (OPTIONAL EVENTS)
Ambient RTD12 Alarm * Analog I/P 1 to 4 Alarm * Bearing RTD 7 Alarm * Bearing RTD 8 Alarm *
Bearing RTD 9 Alarm * Bearing RTD 10 Alarm * Breaker Failure Current Demand Alarm
Gnd Directional Alarm Ground O/C Alarm Input A to G Alarm * Low Fwd Power Alarm
MVA Alarm Mvar Alarm MW Alarm NegSeq Current Alarm
Neut. U/V 3rd Alarm Neutral O/V Alarm Open RTD Alarm Overcurrent Alarm
Overfrequency Alarm Overvoltage Alarm Reactive Power Alarm Reverse Power Alarm
RTD11 Alarm * Short/Low RTD Alarm Stator RTD 1 Alarm Stator RTD 2 Alarm
Stator RTD 3 Alarm Stator RTD 4 Alarm Stator RTD 5 Alarm Stator RTD 6 Alarm
Tachometer Alarm Thermal Model Alarm Trip Coil Monitor Trip Counter Alarm
Underfrequency Alarm Undervoltage Alarm VT Fuse Fail Alarm
OTHER
489 Not Inserted Control Power Applied Control Power Lost Dig I/P Waveform Trig
Input A to G Control * IRIG-B Failure Serial Comm. Start Serial Comm. Stop
Serial Waveform Trip Setpoint 1 Active Setpoint 2 Active Simulation Started
Simulation Stopped Thermal Reset Close Thermal Reset Open
* reflects the name that is programmed