6-28 489 Generator Management Relay GE Multilin
6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS
6
2846 TIME TO TRIP AT 20.0 × FLA 5 to 999999 1 s F10 5
2848 MINIMUM ALLOWABLE VOLTAGE 70 to 95 1 % F1 80
2849 STALL CURRENT @ MIN VOLTAGE 200 to 1500 1 × FLA F3 480
284A SAFE STALL TIME @ MIN VOLTAGE 5 to 9999 1 s F2 200
284B ACCEL. INTERSECT @ MIN VOLT 200 to 1500 1 × FLA F3 380
284C STALL CURRENT @ 100% VOLTAGE 200 to 1500 1 × FLA F3 600
284D SAFE STALL TIME @ 100% VOLTAGE 5 to 9999 1 s F2 100
284E ACCEL. INTERSECT @ 100% VOLT 200 to 1500 1 × FLA F3 500
THERMAL MODEL / THERMAL ELEMENTS
2900 THERMAL MODEL ALARM 0 to 2 1 F115 0
2901 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2902 THERMAL ALARM LEVEL 10 to 100 1 %Used F1 75
2903 THERMAL MODEL ALARM EVENTS 0 to 1 1 F105 0
2904 THERMAL MODEL TRIP 0 to 2 1 F115 0
2905 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
MONITORING / TRIP COUNTER
2A00 TRIP COUNTER ALARM 0 to 2 1 F115 0
2A01 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A02 TRIP COUNTER ALARM LEVEL 1 to 50000 1 Trips F1 25
2A03 TRIP COUNTER ALARM EVENTS 0 to 1 1 F105 0
MONITORING / BREAKER FAILURE
2A20 BREAKER FAILURE ALARM 0 to 2 1 F115 0
2A21 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A22 BREAKER FAILURE LEVEL 5 to 2000 1 × CT F3 100
2A23 BREAKER FAILURE DELAY 10 to 1000 10 ms F1 100
2A24 BREAKER FAILURE ALARM EVENTS 0 to 1 1 F105 0
MONITORING / TRIP COIL MONITOR
2A30 TRIP COIL MONITOR ALARM 0 to 2 1 F115 0
2A31 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A32 TRIP COIL MONITOR ALARM EVENTS 0 to 1 1 F105 0
MONITORING / VT FUSE FAILURE
2A50 VT FUSE FAILURE ALARM 0 to 2 1 F115 0
2A51 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A52 VT FUSE FAILURE ALARM EVENTS 0 to 1 1 F105 0
MONITORING / CURRENT DEMAND
2A60 CURRENT DEMAND PERIOD 5 to 90 1 min F1 15
2A61 CURRENT DEMAND ALARM 0 to 2 1 A F115 0
2A62 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 A F50 16
2A63 CURRENT DEMAND LIMIT 10 to 2000 1 × FLA F14 125
2A65 CURRENT DEMAND ALARM EVENTS 0 to 1 1 A F105 0
MONITORING / MW DEMAND
2A70 MW DEMAND PERIOD 5 to 90 1 min F1 15
2A71 MW DEMAND ALARM 0 to 2 1 F115 0
2A72 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A73 MW DEMAND LIMIT 10 to 200 1 × Rated F14 125
2A75 MW DEMAND ALARM EVENTS 0 to 1 1 F105 0
MONITORING / Mvar DEMAND
2A80 Mar DEMAND PERIOD 5 to 90 1 min F1 15
2A81 Mar DEMAND ALARM 0 to 2 1 F115 0
2A82 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A83 Mar DEMAND LIMIT 10 to 200 1 × Rated F14 125
2A85 Mar DEMAND ALARM EVENTS 0 to 1 1 F105 0
MONITORING / MVA DEMAND
2A90 MVA DEMAND PERIOD 5 to 90 1 min F1 15
2A91 MVA DEMAND ALARM 0 to 2 1 F115 0
2A92 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A93 MVA DEMAND LIMIT 10 to 200 1 × Rated F14 125
2A95 MVA DEMAND ALARM EVENTS 0 to 1 1 F105 0
MONITORING / PULSE OUTPUT
2AB0 POS. kWh PULSE OUT RELAYS (2-5) 1 to 4 1 F50 0
2AB1 POS. kWh PULSE OUT INTERVAL 1 to 50000 1 F1 10
2AB2 POS. kvarh PULSE OUT RELAYS (2-5) 1 to 4 1 F50 0
2AB3 POS. kvarh PULSE OUT INTERVAL 1 to 50000 1 F1 10
2AB4 NEG. kvarh PULSE OUT RELAYS (2-5) 1 to 4 1 F50 0
2AB5 NEG. kvarh PULSE OUT INTERVAL 1 to 50000 1 F1 10
2AB6 PULSE WIDTH 200 to 1000 1 F1 200
Table 6–1: 489 MEMORY MAP (SHEET 19 OF 24)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–33