GE Multilin 489 Generator Management Relay 4-13
4 SETPOINTS 4.3 S2 SYSTEM SETUP
4
4.3.3 GENERATOR PARAMETERS
PATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ GENERATOR PARAMETERS
As a safeguard, when a unit is received from the factory, the PHASE CT PRIMARY and Generator Parameters setpoints will be
defaulted to "--------", indicating they are not programmed. The 489 indicates that it was never programmed. Once these
values are entered, the 489 will be in service. All elements associated with power quantities are programmed in per unit
values calculated from the rated MVA and power factor. The generator full load amps (FLA) is calculated as
(EQ 4.2)
All voltage protection features that require a level setpoint are programmed in per unit of the rated generator phase-phase
voltage.The nominal system frequency must be entered here. This setpoint allows the 489 to determine the internal sam-
pling rate for maximum accuracy. If the sequence of phase rotation for a given system is ACB rather than the standard
ABC, the system phase sequence setpoint may be used to accommodate this rotation. This setpoint allows the 489 to prop-
erly calculate phase reversal and negative sequence quantities.
4.3.4 SERIAL START/STOP INITIATION
PATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ SERIAL START/STOP
If enabled, this feature will allow the user to initiate a generator startup or shutdown via the RS232/RS485 communication
ports. Refer to the Communications chapter for command formats. When a startup command is issued, the auxiliary
relay(s) assigned for starting control will be activated for 1 second to initiate startup. When a stop command is issued, the
assigned relay(s) will be activated for 1 second to initiate a shutdown.
GEN. PARAMETERS
[ENTER] for more
GENERATOR RATED
MVA: ----------------
Range: 0.050 to 2000.000 MVA
“----------” indicates Not Programmed
GENERATOR RATED
POWER FACTOR: -------
Range: 0.05 to 0.99, 1.00
“----------” indicates Not Programmed
GENERATOR VOLTAGE
PHASE-PHASE: --------
Range: 100 to 30000 V in steps of 1
“----------” indicates Not Programmed
GENERATOR NORMAL
FREQUENCY: ----------
Range: 25 Hz, 50 Hz, 60 Hz
“----------” indicates Not Programmed
GENERATOR PHASE
SEQUENCE: -----------
Range: ABC, ACB
“----------” indicates Not Programmed
SERIAL START/STOP
[ENTER] for more
SERIAL START/STOP
INITIATION: Off
Range: On, Off
STARTUP INITIATION
RELAYS (2-5): ----
Range: Any Combination of Relays 2 to 5
SHUTDOWN INITIATION
RELAYS (1-4): ----
Range: Any Combination of Relays 1 to 4
SERIAL START/STOP
EVENTS: Off
Range: On, Off
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Generator FLA
Generator Rated MVA
3 Generator Rated Phase-Phase Voltage×
----------------------------------------------------------------------------------------------------------------------=
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE