4-56 489 Generator Management Relay GE Multilin
4.10 S9 THERMAL MODEL 4 SETPOINTS
4
4.10.2 MODEL SETUP
a) DESCRIPTION
PATH: SETPOINTS ÖØ S9 THERMAL MODEL Ö MODEL SETUP
MODEL SETUP
[ENTER] for more
ENABLE THERMAL
MODEL: No
Range: No, Yes
OVERLOAD PICKUP
LEVEL: 1.01 x FLA
Range: 1.01 to 1.25 × FLA in steps of 0.01
UNBALANCE BIAS
K FACTOR
Range: 0 to 12 in steps of 1
A value of "0" effectively defeats this feature
COOL TIME CONSTANT
ONLINE: 15 min.
Range: 0 to 500 min. in steps of 1
COOL TIME CONSTANT
OFFLINE: 30 min.
Range: 0 to 500 min. in steps of 1
HOT/COLD SAFE
STALL RATIO: 1.00
Range: 0.01 to 1.00 in steps of 0.01
ENABLE RTD
BIASING: No
Range: No, Yes
RTD BIAS
MINIMUM: 40°C
Range: 0 to 250°C in steps of 1
Seen only if ENABLE RTD BIASING is "Yes"
RTD BIAS CENTER
POINT: 130°C
Range: 0 to 250°C in steps of 1
Seen only if ENABLE RTD BIASING is "Yes"
RTD BIAS
MAXIMUM: 155°C
Range: 0 to 250°C in steps of 1
Seen only if ENABLE RTD BIASING is "Yes"
SELECT CURVE STYLE:
Standard
Range: Standard, Custom, Voltage Dependent
STANDARD OVERLOAD
CURVE NUMBER: 4
Range: 1 to 15 in steps of 1. Seen only if SELECT
CURVE STYLE is "Standard"
TIME TO TRIP AT
1.01 x FLA: 17414.5 s
Range: 0.5 to 99999.9 in steps of 0.1. Seen only if
SELECT CURVE STYLE is "Standard"
TIME TO TRIP AT
20.0 x FLA: 20.0 x FLA
Range: 0.5 to 99999.9 in steps of 0.1. Seen only if
SELECT CURVE STYLE is "Standard"
MINIMUM ALLOWABLE
VOLTAGE: 80%
Range: 70 to 95% in steps of 1. Seen only if SELECT
CURVE STYLE is "Voltage Dependent"
STALL CURRENT @ MIN
VOLTAGE: 4.80 x FLA
Range: 2.00 to 15.00 × FLA in steps of 0.01.Seen only if
SELECT CURVE STYLE is Voltage Dependent
SAFE STALL TIME @
MIN VOLTAGE: 20.0 s
Range: 0.5 to 999.9 in steps of 0.1. Seen only if SELECT
CURVE STYLE is "Voltage Dependent"
ACCEL. INTERSECT @
MIN VOLT: 3.80 x FLA
Range: 2.00 to STALL CURRENT @ MIN VOLTAGE in
steps of 0.01. Seen only if SELECT CURVE
STYLE is "Voltage Dependent"
STALL CURRENT @ 100%
VOLTAGE: 6.00 x FLA
Range: 2.00 to 15.00 × FLA in steps of 0.01. Seen only if
SELECT CURVE STYLE is Voltage Dependent
SAFE STALL TIME @
100% VOLTAGE: 10.0 s
Range: 0.5 to 999.9 in steps of 0.1. Seen only if SELECT
CURVE STYLE is "Voltage Dependent"
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Page view 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 258 259

Comments to this Manuals

No comments