4-76 489 Generator Management Relay GE Multilin
4.12 S11 ANALOG I/O 4 SETPOINTS
4
4.12.2 ANALOG INPUTS 1 TO 4
PATH: SETPOINTS ÖØ S11 ANALOG I/O ÖØ ANALOG INPUT 1(4)
Table 4–8: ANALOG OUTPUT PARAMETER SELECTION
PARAMETER NAME RANGE / UNITS STEP DEFAULT
MIN. MAX
IA Output Current 0.00 to 20.00 × FLA 0.01 0.00 1.25
IB Output Current 0.00 to 20.00 × FLA 0.01 0.00 1.25
IC Output Current 0.00 to 20.00 × FLA 0.01 0.00 1.25
Avg. Output Current 0.00 to 20.00 × FLA 0.01 0.00 1.25
Neg. Seq. Current 0 to 2000% FLA 1 0 100
Averaged Gen. Load 0.00 to 20.00 × FLA 0.01 0.00 1.25
Hottest Stator RTD –50 to +250°C or –58 to +482°F 1 0 200
Hottest Bearing RTD –50 to +250°C or –58 to +482°F 1 0 200
Ambient RTD –50 to +250°C or –58 to +482°F 1 –50 60
RTDs 1 to 12 –50 to +250°C or –58 to +482°F 1 –50 250
AB Voltage 0.00 to 1.50 × Rated 0.01 0.00 1.25
BC Voltage 0.00 to 1.50 × Rated 0.01 0.00 1.25
CA Voltage 0.00 to 1.50 × Rated 0.01 0.00 1.25
Volts/Hertz 0.00 to 2.00 × Rated 0.01 0.00 1.50
Frequency 0.00 to 90.00 Hz 0.01 59.00 61.00
Neutral Volt. (3rd) 0 to 25000 V 0.1 0.0 45.0
Average Voltage 0.00 to 1.50 × Rated 0.01 0.00 1.25
Power Factor 0.01 to 1.00 lead/lag 0.01 0.8 lag 0.8 lead
Reactive Power (Mvar) –2.00 to 2.00 × Rated 0.01 0.00 1.25
Real Power –2.00 to 2.00 × Rated 0.01 0.00 1.25
Apparent Power 0.00 to 2.00 × Rated 0.01 0.00 1.25
Analog Inputs 1 to 4 –50000 to +50000 1 0 50000
Tachometer 0 to 7200 RPM 1 3500 3700
Thermal Capacity Used 0 to 100% 1 0 100
Current Demand 0.00 to 20.00 × FLA 0.01 0.00 1.25
Mvar Demand 0.00 to 2.00 × Rated 0.01 0.00 1.25
MW Demand 0.00 to 2.00 × Rated 0.01 0.00 1.25
MVA Demand 0.00 to 2.00 × Rated 0.01 0.00 1.25
ANALOG INPUT 1
[ENTER] for more
ANALOG INPUT1:
Disabled
Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA
ANALOG INPUT1 NAME:
Analog I/P 1
Range: 12 alphanumeric characters
ANALOG INPUT1 UNITS:
Units
Range: 6 alphanumeric characters
ANALOG INPUT1
MINIMUM: 0
Range: –50000 to 50000 in steps of 1
ANALOG INPUT1
MAXIMUM: 100
Range: –50000 to 50000 in steps of 1
BLOCK ANALOG INPUT1
FROM ONLINE: 0 s
Range: 0 to 5000 sec. in steps of 1