4-74 489 Generator Management Relay GE Multilin
4.11 S10 MONITORING 4 SETPOINTS
4
4.11.6 PULSE OUTPUT
PATH: SETPOINTS ÖØ S10 MONITORING ÖØ PULSE OUTPUT
The 489 can perform pulsed output of positive kWh and both positive and negative kvarh. Each output parameter can be
assigned to any one of the alarm or auxiliary relays. Pulsed output is disabled for a parameter if the relay setpoint is
selected as OFF for that pulsed output. The minimum time between pulses is fixed to 400 milliseconds.
This feature should be programmed so that no more than one pulse per 600 milliseconds is required or the pulsing
will lag behind the interval activation. Do not assign pulsed outputs to the same relays as alarms and trip functions.
Figure 4–22: PULSE OUTPUT
4.11.7 GENERATOR RUNNING HOUR SETUP
PATH: SETPOINTS ÖØ S10 MONITORING ÖØ RUNNING HORU SETUP
The 489 can measure the generator running hours. This value may be of interest for periodic maintenance of the generator.
The initial generator running hour allows the user to program existing accumulated running hours on a particular generator
the relay is protecting. This feature switching 489 relays without losing previous generator running hour values.
PULSE OUTPUT
[ENTER] for more
POS. kWh PULSE OUT
RELAYS (2-5): ----
Range: Any combination of Relays 2 to 5
POS. kWh PULSE OUT
INTERVAL: 10 kWh
Range: 1 to 50000 kWh in steps of 1
POS. kvarh PULSE OUT
RELAYS (2-5): ----
Range: Any combination of Relays 2 to 5
POS. kvarh PULSE OUT
INTERVAL: 10 kvarh
Range: 1 to 50000 kvarh in steps of 1
NEG. kvarh PULSE OUT
RELAYS (2-5): ----
Range: Any combination of Relays 2 to 5
NEG. kvarh PULSE OUT
INTERVAL: 10 kvarh
Range: 1 to 50000 kvarh in steps of 1
PULSE WIDTH:
200 ms
Range: 200 to 1000 ms in steps of 1
RUNNING HOUR SETUP
[ENTER] for more
INITIAL GEN. RUNNING
HOURS: 0 h
Range: 0 to 999999 h in steps of 1
GEN. RUNNING HOURS
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
GEN. RUNNING HOURS
LIMIT: 1000 h
Range: 1 to 1000000 h in steps of 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE
808738A1.CDR
PULSE
WIDTH
normally open (NO) contact
normally closed (NC) contact
status
OPEN
CLOSED
status
CLOSED
OPEN
status
OPEN
CLOSED
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE