Digital Output Tab
Digital Input Form
This tab is available only if you have selected Digital Output in the Type field on the Digital Input Tab. Use
this tab to link digital outputs to a digital input. When this digital input is activated, the digital output is also
triggered.
Output A (Primary/Local: A primary input assignment is not required. The default is None. Click the
drop-down list to select an available DO to assign as the primary. If you select an output, this output must
belong to the local micro. If the micro is offline or unable to communicate with the host at the time of an
alarm, only the Primary/Local DO is triggered.
If the ON time on the Digital Output Form is set to 00, this DO will remain active until the digital input is
reset.
Output B:
Click the drop-down list to select an available DO. The digital outputs in this list can be on a local micro or
other micros. Output B will be activated only if the host is online and able to communicate with other
micros.
Digital Output Tab
Digital Output Form
Use this tab to schedule when the digital outputs in the group are in the active state and for the specified
length of time.
Micro
This is a read-only field. Displays the description of the micro on which this digital output is located.
Board
This is a read-only field. When the records are created, the default value is in the format: mmmm-b Board
Type where mmmm represents the micro number to which this reader is associated, b represents the
board number, and Board Type is the type of reader board, such as 16DO.
Example: 0001-1 16DO would be the digital output on micro one, 16DO board one.
Number
This is a read-only field. Displays the number of the digital output.
Active state
On/Off: Defines whether the digital output will be turned On or Off when the digital output is activated.
Contact your installer on how the digital output was wired. This determines the active state of the digital
output.
On time: Specifies the length of time the digital output will remain in the active state before going
inactive. This time may be overridden by the manual control buttons. If you enter 0 and this is:
Output A, then the digital output will reset when the alarm resets.
Output B, then the digital output will remain on until it is manually turned off or scheduled off.
When a micro is reset or the database is reloaded, all schedules from midnight to present time will run
EXCEPT for schedules that have a DO On time NOT equal to zero and were set to occur prior to the
current time. For example, you have created a schedule to occur at 8:00 am to turn a digital output into
the active state for 1 minute. At 10:00 am, the database for the micro is downloaded. During the
download process all schedules from Midnight to the current time (10:00 am) are re-run. Your schedule
for the DO will not run since it started and ended before the current time of 10:00 am.