Installation Instructions
DUCTWORK CALCULATIONS
Calculate Total Equivalent Ductwork Length
Equivalent Number Equivalent
Duct Pieces Length* x Used = Length
6round
straight 1 ft. x ( )
= ft.
3
1
4x 10
straight 1 ft. x ( )
= ft.
6, 90°
elbow 15 ft. x ( ) = ft.
6, 45°
elbow 9 ft. x ( ) = ft.
24max.
Flexible
Metal Offset
Adapter 34 ft. x ( ) = ft.
3
1
4x 10
90° elbow 16 ft. x ( ) = ft.
3
1
4x 10
45° elbow 5 ft. x ( ) = ft.
3
1
4x 10
90° flat elbow 18 ft. x ( ) = ft.
6round
to 3
1
4x 10
transition 7 ft. x ( ) = ft.
Subtotal Column 1 = ft.
*Equivalent lengths of duct pieces are based on
actual tests and reflect requirements for good venting
performance with any downdraft cooktop.
† Measure and list feet of straight duct used. Count
and list the quantity of all other duct pieces for the
“Number Used” of each type.
IMPORTANT
For maximum efficiency, use the shortest and
straightest duct run possible, with as few fittings as
possible. For satisfactory performance, the duct run
should not exceed 100 feet equivalent length.
Venting performance is improved by using larger
diameter duct.
Equivalent Number Equivalent
Duct Pieces Length* x Used = Length
6round
to 3
1
4x 10
transition
90° elbow 20 ft. x ( ) = ft.
3
1
4x 10
to 6round
transition 5 ft. x ( ) = ft.
3
1
4x 10
to 6round
transition
90° elbow 12 ft. x ( ) = ft.
6round
wall cap
with damper 21 ft. x ( ) = ft.
3
1
4x 10
wall cap
with damper 27 ft. x ( ) = ft.
6round
roof cap 20 ft. x ( ) = ft.
6round
roof vent 24 ft. x ( ) = ft.
Subtotal Column 2 = ft.
Subtotal Column 1 = ft.
TOTAL DUCTWORK = ft.
Should not exceed 100 feet.
DO NOT use flexible plastic ducting.
Vent installation should not exceed 100 feet
equivalent length.