3-16 Section 3: Installation
February 3, 2000 70055MP Revision D
After-Market
Use the following procedure to wire an After-Market Tap Position Indicator.
1. Verify that the signal output is one of the following:
- 5V to + +5 VDC
-10 to + 10 VDC,
0 to +5 VDC, or
0 to +10 VDC.
2. Connect the signal output to Sensor Input #8.
3. Connect the signal reference to a Sensor Common Terminal.
NOTE: Tap Position must be calibrated to operate correctly (see Calibrate
Tap Position).