GE NX-8V2 User Manual Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
NX-8V2 Control 57
MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS
(Residential Fire, Residential Burglary, Commercial Burglary)
The NetworX NX-8V2 panel is necessary to initiate Residential and Commercial installations.
At least one compatible keypad is needed for all applications.
At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the AD10-12 bell
and Grade A bell housing shall be used.
Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
A minimum of two (2) keypads is required for Home Health applications and each keypad must be set to a unique address.
The wireless devices are only UL listed for residential applications.
The DACT shall be enabled for all commercial burglary applications.
STANDBY TIME TOTAL AUXILIARY
CURRENT
STANDBY BATTERY
CAPACITY
ALARM CURRENT
24 hours 1.9 Amps 51 AH 600 mA
1.25 Amps 34 AH 1 Amp
600 mA 17 AH 1 Amp
48 hours 900 mA 51 AH 1 Amp
600 mA 34 AH 1 Amp
300 mA 17 AH 1 Amp
72 hours 600 mA 51 AH 1 Amp
400 mA 34 AH 1 Amp
200 mA 17 AH 1 Amp
Calculations based on three 17-Amp batteries.
K
IMPORTANT!
If separate power supplies are necessary to accommodate additional devices, safety standards require that each power
supply be prominently marked with adequate instructions for removing all power from the unit.
Dispose of used batteries according to the manufacturer’s instructions and/or local government authorities.
Installation personnel should thoroughly read and understand the installation instructions and the users manuals for the panel
and all the accessories to be included with the system before attempting to install a security system.
WARNING!
Replace only with Panasonic #LC12V4BP or Yuasa #NP4-12 battery. Observe polarity when installing a new battery.
Installing the battery backwards may cause damage to the panel. There is a risk of explosion if the battery is replaced with an
incorrect type.
NOTE
Electrical codes will vary depending upon the country and city where the system is installed. It is the installer’s responsibility
to ensure that the electrical installation is safe and conforms to all applicable codes, laws, or regulations. Only qualified
persons should connect this device to the mains supply.
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60

Comments to this Manuals

No comments