GE NX-8V2 User Manual Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
NX-8V2 Control 19
36 PARTITION SELECT, ZONES 41-48 8............. feature select
Location 36 is used to select the partition or partitions that zones 41-48 reside in. A zone may reside in any combination of the 8
partitions. If a burglary zone resides in more than 1 partition it will only be active when all partitions are armed. A zone that
resides in more than 1 partition will be reported to its lowest partition. Location 36 has 8 segments. Segment 1 corresponds to
zone 41 and Segment 8 corresponds to zone 48.
Segments 1 - 8:
1 = Partition 1 3 = Partition 3 5 = Partition 5 7 = Partition 7
2 = Partition 2 4 = Partition 4 6 = Partition 6 8 = Partition 8
L 37 SIREN AND SYSTEM SUPERVISION 7............. feature select
Location 37 is used to enable various system feature and reporting options. (For specific definitions, refer to the Glossary beginning on
page 46)
Segment 1:
1 = On if siren sounds for "Telephone Line Cut" when armed.
2 = On if siren sounds for "Telephone Line Cut" when disarmed.
3 = On if siren blast at arming.
4 = On if siren blast at exit expiration.
5 = On if siren blast at closing kissoff.
6 = On if siren sounds during a "Cross Zone" verification time.
7 = On if siren sounds for a Zone or Box Tamper.
8 = On if siren blasts 1 time for keyswitch or wireless arming; 2 times for disarming.
(Note: Must be disabled for SIA CP-01 installations.)
Segment 2:
1 = On if siren driver should be a voltage output. Off if on board siren driver enabled.
2 = On if siren sounds for expander trouble (required for UL installations).
3 = On for Immediate Restore by zone. Off for zones to restore only when siren is off.
4 = On if Dynamic Battery Test performed at arming. Off if performed at disarming. (See location 40)
5 = On if Battery Missing Test is performed every 12 seconds.
6 = On if Manual Bell Test performed during [r]-[4]-[4] test function.
7 = On if Manual Communicator Test performed during [r]-[4]-[4] test function.
8 = On if Box Tamper terminals on the control panel are enabled.
Segment 3:
1 = On if Box Tamper report enabled.
2 = On if AC Fail reporting enabled.
3 = On if Low Battery reporting enabled.
4 = On if Aux. Power Overcurrent report enabled.
5 = On if Siren Supervision report enabled.
6 = On if Telephone Line Cut report enabled.
7 = On if Ground Fault Detection report enabled.
8 = On if Expander Trouble reporting enabled.
Segment 4:
1 = On if Fail To Communicate report enabled.
2 = On if Log Full report enabled.
3 = On if Autotest report enabled.
4 = On if Start/End programming report enabled.
5 = On if End Download report enabled.
6 = On if Sensor Low Battery report enabled.
7 = On if Sensor Missing report enabled.
8 = On if First to Open / Last to Close.
Segment 5:
1 = On enable Lost Clock service light.
2 = On enables Zone Doubling (requires NX-200 Zone Doubling Kit).
3 = On disables On-Board 8 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = Reserved.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: Do NOT disable for UL listed systems.