Exiting Failsafe
Failsafe Handling
Failsafe Examples One and Three
Table 12 and Table 13 list two failsafe examples. Table 14 and Table 15 on page 179
cover two more fail-safe examples. Detailed instructions for exiting failsafe follow these
tables.
Exiting Failsafe
Use this procedure to exit the failsafe mode for cases one and three:
Step One
1. Restore the air supply or correct the actuator problem.
2. Check that the pneumatics are working correctly.
3. Move the Failsafe dialog box to one side of the screen to uncover the IVI display.
4. If the PID dialog box is open, close it.
Step Two
Table 12 Failsafe Case One
Case One Failsafe Type Actuator
Action
Cause of Failure
Observable Behavior: Valve fails
closed with low actuator pressure.
After pressure problem is corrected the
valve is closed in failsafe.
Deviation
Error
Air to Open
Fail Close
Loss of supply or low actuator
pressure
XD Error: Deviation error appears in
the error status. The Failsafe Status
dialog box displays and shows Active,
Latched.
Table 13 Failsafe Case Three
Case Three Failsafe Type Actuator
Action
Cause of Failure
Observable Behavior: Valve fails to
open with high actuator pressure. After
pressure problem is corrected the
valve is closed in failsafe.
Deviation
Error
Air to Open
Fail Close
High actuator pressure
XD Error: Deviation error appears in
the error status. The Failsafe Status
dialog box displays and shows Active,
Latched.