Error Messages
Auto Tune Results
Table 16 Auto Tune Results
Reference Message Possible Cause
1 Succeeded
2 Canceled Operator selected cancel
21 Exhaust air pressure warning
22
Small air supply pressure
warning
23
Large air supply pressure
warning
40 Offset drift warning
42
Large response speed
warning
43 Large hysteresis warning
44 Large slip width warning
60
Small angle span warning The position is incorrectly configured as rotary
on a linear, reciprocating, valve.
61
Large angle span warning The position is incorrectly configured as linear
reciprocating on a rotary valve.
62
Fifty percent angle warning At mid-scale the position sensor angle is
greater than 15° from horizontal.
100 Small angle span error
101 Large angle span error