EPM Device- Special Considerations CIMPLICITY PMCS Read-This-Book-First
EPM Software Components
There are four major components of the EPM software. The Network Builder, ION
Designer, Communications Server, and ION_LINK DDE Server each interact to
support the EPM 7700, EPM 7600 and EPM 7500 Meters. When you selected the
“PMCS with EPM 7700 Components” selection during the PMCS installation
routine, these software components were installed automatically. The four
components and their functions are described below.
Network Builder: Building the Network
Configuration File
The Network Builder presents a graphical view of the EPM 7700, EPM 7600 and
EPM 7500 devices in your network, allowing you to easily add, remove or configure
sites, services and meters. Network Builder creates a central network configuration
file that holds information for the workstation, the network connections, and every
connected device. You may want to restrict access to Network Builder or the
network configuration file, since if the file is tampered with, EPM 7700, EPM 7600
and EPM 7500 components may be rendered inoperable.
ION Designer: Programming Devices and Software
Nodes
The ION Designer component allows you to customize the operation of an ION-
compliant node, such as 7000-series meters and 3000-series meters. Be aware that
misuse of ION Designer can adversely affect the operation of your meters.
IMPORTANT: For purposes of PMCS network compatibility, it is CRITICAL that
any EPM 7700, EPM 7600 and EPM 7500 meters be configured with the GE PMCS
standard configuration. Using ION Designer to customize EPM 7700, EPM 7600 or
EPM 7500 functionality can compromise compatibility with the PMCS client
applications attempting to access the device.
Communications Server: System Communications
The Communications Server is the core communications component for EPM 7700,
EPM 7600 and EPM 7500 meters. The Communications Server manages all
communications between the meters connected to your network and the GE77GTWY
and ION_Link DDE Server software applications.
ION_LINK DDE Server: Communication with
Windows Applications
The ION_LINK DDE Server uses Dynamic Data Exchange to share information
with applications such as Microsoft Excel or the CIMPLICITY Wizards.