CIMPLICITY PMCS Read-This-Book-First Configuring the Software
47
Configuration Procedure
Follow the procedure below to efficiently configure your system and minimize your
time to startup.
Host PC Configuration
1. Configure the DDE Server. Your Host PC will likely have several versions of
the DDE Server installed (RS485-Modbus, TCP/IP Modbus, TCP/IP
Encapsulated Modbus and Ethernet-TCP/IP). Configure only the server
appropriate for your PMCS network interface (GE32MODB, GE32MTCP,
GE32GTWY or GE32ENET). See GEH-6510, Network and Device
Configurator, for complete details.
2. EPM 7700, EPM 7600 and EPM 7500 users only (all others proceed to step
3): Configure the Communications Server and GE 7700 Gateway Server. If you
installed the EPM software options and you are going to use EPM 7700, EPM
7600 or EPM 7500 devices in your PMCS network, you will need to configure
both the Communications Server and the GE 7700 Gateway Server. For Comm
Server configuration instructions, refer to EPM Software Components
Configuration later in this guide. For GE 7700 Gateway Server configuration
instructions, refer to DEH-40035, the GE 7700 Gateway Server User’s Guide.
3. Configure the user interface. If your system was provided with a generic HMI
software application, either load or create the custom HMI (using the Interface
Toolkit wizards, if appropriate; see DEH-210, CIMPLICITY PMCS Interface
Toolkit or refer to the HMI software’s documentation.
4. Configure the applications. As appropriate, configure the following application
modules, referring to the instruction manuals provided.
Event Logger, GEH-6512
Waveform Capture, GEH-6511
5. Test the applications. Test the functioning of all applications to ensure proper
Host PC operation. Do not proceed to step 5 until you are sure the Host PC
operates as expected.
6. Set up NetDDE. If your system has one or more View Nodes, set up NetDDE
shares and trusts in the Host PC, following the procedures in GEH-6510,
Network & Device Configurator and the CIMPLICITY HMI documentation.
7. Set up NetDDE. If your system uses the PMCS Waveform Capture client, and
you intend to access waveform data from View Nodes, set up NetDDE shares
and trusts for the PMCS Waveform Server following the procedures in GEH-
6511, PMCS Waveform Capture Module.
Viewer Workstation Configuration
1. Configure the user interface. Load the custom MMI. Refer to the CIMPLICITY
HMI documentation as appropriate.
2. Configure the applications. As appropriate, configure the application modules,
referring to the instruction manuals provided. See step 3 of the Host PC
Configuration for the appropriate instruction manual numbers.