Configuring the Software CIMPLICITY PMCS Read-This-Book-First
EPM Software Components Configuration
The EPM 7700, EPM 7600 and EPM 7500 requires several separate software
components which are installed during the PMCS setup. This section provides a brief
overview of the steps required to configure these components; the following section
describes the EPM software components in greater detail.
For details of using the NetBuilder software, refer to the Configuring the EPM 7700
Device Network section of this manual, and to DEH-440035, the GE 7700 Gateway
User’s Guide.
1. Launch the NetBuilder application. From the Start menu, select
Programs>Power Management Ltd>Utilities>Network Builder.
2. Insert a workstation(s). Normally all the workstations in a PMCS network are
automatically configured during the installation of the software – these
instructions are provided in case you need to enter the information manually.
Select the Items menu from NetBuilder, and choose Workstation to insert a
workstation. Name the workstation (up to 15 alphanumeric characters, the first
character must be alphabetic), and choose OK. Repeat this step for each
workstation (computer) in your network.
3. Insert Ethernet Sites. Select Items>Insert>Ethernet Site to insert an Ethernet site.
Set the proper time synchronization options, then choose OK. Repeat this step to
add additional sites to the workstation if necessary.
4. Insert devices to the site. Select Items>Insert>Device, and complete the dialog
box with the proper device type, Group, Ethernet address and name for an
Ethernet device (EPM 7700, EPM 7600 or EPM 7500). The device name may
be no more than eight alphanumeric characters, and the first character must be
alphabetic. The IP service port field must be "7700" for any device connected to
the Ethernet, and "7800" for any additional device connected through an EPM
7700’s RS485 port. Choose OK to close the Insert Device dialog box. Repeat
this step as necessary to add additional devices to the site.
5. Save and exit. When all workstations, sites, and devices have been added, select
the save icon and then exit.