Low Signal Value Calibration
Calibrate Screen
Figure 95 Starting Signal Calibration
2. Click OK and Figure 96 appears with a field to enter the low or high signal value.
Figure 96 Signal Calibration Dialog
3. Enter a low value Signal Value (from 3.5 and 8.0 mA) and click Set as Low Value.
Figure 97 Setting Signal Low Value
NOTE Enter a low signal value outside the 3.5 to 8.0 range and
Figure 98 appears. Click OK and re-enter the value.
Figure 98 Low Signal Calibration Warning