8 | GE Oil & Gas
SIL 2 Capability for Enhanced Safety
The 12400 Series transmitter, SIL2-certified in accordance with IEC61508 per EXIDA, is suitable for
use in safety instrumented functions.
The safety function of the 12400 Series transmitter is not limited to the instrument head but also includes all
measurement components.
The FMEDA analysis results include the entire transmitter from displacer through the torque tube, the sensor,
and the electronics up to the 4-20 mA output signal. In contrast, other available devices limit their analysis to
the instrument head only.
Including all measurement components in the safety function means a higher diagnostic coverage and a Safe
Failure Fraction greater than 90 percent.
Complete Safety Function: From Displacer Up to Analog Output Signal
The 12400 Series instrument has been enhanced with a new sensor bias sub-assembly to enable a better
diagnostic coverage of internal and user faults. Following in the footsteps of many other innovations that have
made GE’s Masoneilan product line a technology leader, this new patented solution improves the diagnostic
analysis on all components between the sensor and the torque rod. In case of failure caused by a loose part or
human error, the spring arm will force the sensor to go into the repeatable failsafe position.
This is particularly useful in detecting the main faults that are often human errors during the coupling procedure.
For instance, the wrong coupling or a loose coupling between the sensor mechanism and the torque rod can occur
when the work is done by untrained people. These errors are now fully detected and diagnosed, and they will
generate a HART fault message and could even activate one of the two optional switches.
Enhanced Diagnostic Coverage
Normal operating
Coupling correctly done
Failure diagnostic
Loosen coupling
The spring arm forces
the sensor to go in
failsafe position.