GE EPM 5300 User Manual Page 89

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 88
CHAPTER 15: PROGRAMMING QUICK REFERENCE
GE Industrial Systems 5300P Advanced Power Meter 85
CHAPTER 15
PROGRAMMING QUICK REFERENCE
15.1: Entering the Programming Mode
1. Hold PHASE/NEXT key and press AMPS key.
2. Display blanks and shows either a ‘0’,
‘1’, or ‘3’.
3. If ‘3’ is not displayed then press AMPS key until ‘3’ is displayed.
4. Release AMPS key and press PHASE/NEXT key, while ‘3’ is still displayed.
5. Display shows ‘333’ momentarily.
6. Upper display starts counting. Press PHASE/NEXT key when ‘5’ is displayed to register the ‘5’.
7. Repeat step 6 until ‘555’ has been registered.
15.2: Data Entry Sequence
1. At programmable numerical fields or Switch Pack fields, Press AMPS key to begin Data Entry
Sequence.
2. The current setting moves to middle row of display and dashes appear in the bottom row. Press
VOLTS key to toggle between available choices.
3. When a correct choice is selected, press AMPS key to store.
15.3: Programming Groups
Programming
groups
Description
0
Global Meter Setup—Integration Interval, Meter Address,
Communication Setting, Relay Settings
1
Full Scale Settings. Voltage Full Scale, Current Full Scale and Power
Function Full Scale.
2
Meter Calibration
3
Calibration Ratios
4
Volts and Current Limits
5
Power Function Limits
6
THD Limits
7
Imbalance Reversal Limits
8
DC Output Calibration
Page view 88