GE EPM 5300 User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
CHAPTER 4: COMMUNICATION INSTALLATION
GE Multilin EPM 5000 series Advanced Power Meters 21
RS-485 Hookup Diagram (4 wire) Full Duplex
T+ T-R-R+
PC
UNICOM 2500
(Bottom View Shown)
RS-232
RS-485
Note: This does not
represent a twisted pair. It
shows the cross-over from R
to T between the Unicom
and the rest of the bus.
5300P Instruments (rear view)
RS-485
Communications Port
Model#SF485DB
Figure 4.5: 4-Wire RS-485 Communication Connection Installation full duplex
—Detail view on following page
Connecting 4-Wire bus to RS-485 Port:
Connect the T- wire of the Unicom 2500 to the R- on the RS-485 port
Connect the R- wire of the Unicom 2500 to the T- on the RS-485 port
Connect the T+ wire of the Unicom 2500 to the R+ on the RS-485 port
Connect the R+ wire of the Unicom 2500 to the T+ on the RS-485 port
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 99 100

Comments to this Manuals

No comments