3. Align inside of mounting arm with studs and slide it into
place against pole.
4. Install luminaire and secure with flat washers and
locknuts provided. See Figure 4.
Caution: Ensure that the nuts fully engage the two
studs. Correct tightening of nuts is important to
ensure proper function of mounting system.
Torque nuts to 18-22 foot-pounds (24.4 - 29.8 N•m).
5. Replace SnapDrive and reflector, reconnect socket leads
and wire harness.
B. WIRING
Make all electrical connections in accordance with
all applicable code requirements (National Electrical
Code, Canadian Electrical Code and applicable local
Codes).
Verify that supply voltage is correct by comparing it
to nameplate.
Route wire harness leads from luminaire through
arm and into top of pole. Connect wire harness to
supply wire and return to interior of pole. Replace
pole cap.
Supply wiring entering from pole to interior termi-
nal board must be routed through the wiring clips
and maintain one-half inch (1/2”) (13mm) minimum
spacing to SnapDrive (see Figure 1).
Connect ground lead to the green lead, green
ground screw on housing or terminal block pro-
vided.
The 1000 watt SnapDrive is equipped with a multi-volt
ballast. Ballast has been wired to the voltage indicated on
the nameplate. Verify that supply voltage is correct by
comparing it to nameplate. If another voltage is desired,
place the voltage selection jumper onto the appropriate
voltage position as indicated on the wiring diagram.
Optional features such as fusing, switched quartz safety
lights and photocontrols are voltage specific. Do not
change jumper positions if fixture is equipped with these
features. This will damage or destroy these optional parts
and will void the safety listing (UL, CUL, CSA, etc.) of the
fixture.
The 750 watt SnapDrive is discrete voltage only. Voltage
selector should not be moved.
Replace power fuses only with fuses of the same type and
ratings.
To complete installation refer to MOUNTING.
Figure 3
ROUND POLE MOUNTING:
MUST SPECIFY ROUND POLE ADAPTER ACCESSORY.
DRILLING TEMPLATE
Figure 2
SQUARE POLE MOUNTING: STANDARD
DRILLING TEMPLATE
Figure 2
SQUARE POLE MOUNTING: STANDARD
DRILLING TEMPLATE
1.312 in.(33mm)
.656 in.(17mm)
1.812 in.
(46mm)
1.250 in. DIA
(32mm DIA)
HOLE
5.250 in.
(133mm)
MIN
.312 in.(8mm) DIA HOLE
.438 in.(11mm) DIA HOLES
2.196 in.
(56mm)
4.392 in.
(112mm)
5.250 in.
(133mm)
MIN
.438 in.(11mm) DIA HOLES
1.250 in. DIA
(32mm DIA)
HOLE
2.719 in.
(69mm)
5.438 in.
(138mm)
Figure 4
STUDS
SQUARE
POLE
MOUNTING ARM
NUTS (3/8 - 16)
WASHERS
SCREW (1/4 - 20)
Page view 1