26 GE Zenith Controls
Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)
Standard Transition
Each MX250 microprocessor based ATS controller
requires a relay/transformer box to apply line voltage to
the ATS operator via coil control relays. Also required is
power for the MX150 printed circuit board and an appli-
cation of sensing voltage proportional to line voltage.
This is accomplished by the relay transformer box. This
method of switching operator voltage and applying power
and sensing voltage to the printed circuit board isolates
R/T Box Primary 1 VA 25 VA
Assembly Voltage XFMR XFMR
Part No. at 50/60 Hz Part No. Part No.
57P-1015 120V K-3216 K-3224
57P-1016 208-220V K-3217 K-3225
57P-1017 230-240V K-3218 K-3226
57P-1018 277V K-3219 K-3227
57P-1019 380-400V K-3220 K-3228
57P-1020 416-440V K-3221 K-3229
57P-1021 460-480V K-3222 K-3230
57P-1022 575-600V K-3223 K-3231
Relay/Transformer (R/T Box)
40-225 Amp Molded Power Section
Transformer Usage (see Figure 12)
Item Part No. Description Qty
1 See Chart Transformer (1 VA) 2
2 See Chart Transformer (25 VA) 2
3 K-1274 Relay Flange Mounted 2
Bill of Material
R/T Box Primary 1 VA 25 VA
Assembly Voltage XFMR XFMR
Part No. at 50/60 Hz Part No. Part No.
50P-1026 120V K-3216 K-3224
50P-1027 208-220V K-3217 K-3225
50P-1028 230-240V K-3218 K-3226
50P-1029 277V K-3219 K-3227
50P-1030 380-400V K-3220 K-3228
50P-1031 416-440V K-3221 K-3229
50P-1032 460-480V K-3222 K-3230
50P-1033 575-600V K-3223 K-3231
40-3000 Amp - All Other Standard Types
Transformer Usage (see Figure 13)
Item Part No. Description Qty
1 See Chart Transformer (25 VA) 2
2 See Chart Transformer (1 VA) 2
3 K-1260 Coil Control Relay (24V) 2
Bill of Material
SEC.
PRI.
SEC.
PRI.
SEC.
PRI.
the MX250 from the line voltage, further protecting
the controller from harmful line transients. Two versions
of the R/T box exist depending on the type of ATS
(standard transition or delayed transition).
The following layout drawings of the R/T Box compo-
nents (standard and delayed transition) include a bill of
materials for replacement parts. Schematics are included
to indicate proper wiring.
1
2
(inside)
3
1
2
3
Figure 13
Figure 12
Page view 25