Ge GFK-2193A User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 30
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
GFK-2193A Chapter 2 Installation 2-3
2
PROFIBUS Cable Types
The recommended cable is
Belden 3079A PROFIBUS Cable
This is a shielded, 150 ohm twinaxial (single twisted pair) cable. It has 22 AWG
conductors and a mutual capacitance of 9.0 pF per foot, nominal. For complete
specifications on this cable, please contact your Belden dealer or visit their website at
www.belden.com.
Alternate cable types are:
Siemens 6XV1 830-OAH10 Two Core shielded
Siemens 6XV1 830-OBH10 w/PE Sheath
Siemens 6XV1 830-3AH10 for underground burial
Siemens 6XV1 830-3BH10 trailing cable
Bosch Comnet DP #913 548 Flexible PROFIBUS cable
Bosch Comnet DP #917 201 Trailing PROFIBUS Cable
Bosch Comnet DP #917 202 Massive PROFIBUS Cable
Note: Allen Bradley “blue hose,” which has an impedance of 78 ohms, is not
recommended for this application.
Network Termination
Termination resistors are needed, as defined in DIN 19245 Part 1 section 3.1.2.5.
Master Slave Slave Slave SlaveSlave
Termination Required
(Segment 1)
One terminator must be applied at each end of a network segment.
Master Slave Slave Slave SlaveSlave
Repeater
Termination Required
(Segment 1)
Term ination Required
(Segment 2)
Generally, termination is provided in commercially-available PROFIBUS standard network
connectors. Some connector vendors provide termination capability in the connector and
a switch on the connector to enable/disable termination. Some connector vendors provide
both terminated and unterminated connectors.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 29 30

Comments to this Manuals

No comments