The parameters available with the SCROLL buttons are listed below:
Mode Description
RMS Current Units in Amps; phase shifting among A, B, and C.
RMS Voltage L-N
Units in Volts; available only in Wye configuration, with phase shifting
among A, B, and C.
RMS Voltage L-L Units in Volts; phase shifting among AB, BC, and CA.
Watts Units in kW; phase shifting among A, B, C, and total.
Vars Units in kVARs; phase shifting among A, B, C, and total.
Volt-Amps Units in kVA; phase shifting among A, B, C, and total.
Power Factor No units; no phase shifting.
Watt-Hours Units in kWH; no phase shifting.
VAR-Hours Units in kVARH; no phase shifting.
Current Demand Units in A; phase shifting among A, B, and C.
Peak Current Units in A; phase shifting among A, B, and C.
Watt Demand Units in kW; no phase shifting.
Peak Watt Demand Units in kW; no phase shifting.
Frequency Units in Hz; no phase shifting.
Harm Distortion
Value area of display is blank; degree of harmonic distortion is shown as
negligible, mild, moderate, or severe.