GE DEH-210 User Manual Page 218

  • Download
  • Add to my manuals
  • Print
  • Page
    / 220
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 217
212 Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM 3720 PMCS Interface Toolkit
#1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Class Sub-class Instance Meaning
ED I2 HD - Harmonic #13 STD TD SD PD
EE I3 HD - Harmonic #13 STD TD SD PD
EF I4 HD - Harmonic #13 STD TD SD PD
F0 V1 HD - Harmonic #14 STD TD SD PD
F1 V2 HD - Harmonic #14 STD TD SD PD
F2 V3 HD - Harmonic #14 STD TD SD PD
F3 VAUX HD - Harmonic #14 STD TD SD PD
F4 I1 HD - Harmonic #14 STD TD SD PD
F5 I2 HD - Harmonic #14 STD TD SD PD
F6 I3 HD - Harmonic #14 STD TD SD PD
F7 I4 HD - Harmonic #14 STD TD SD PD
F8 V1 HD - Harmonic #15 STD TD SD PD
F9 V2 HD - Harmonic #15 STD TD SD PD
FA V3 HD - Harmonic #15 STD TD SD PD
FB VAUX HD - Harmonic #15 STD TD SD PD
FC I1 HD - Harmonic #15 STD TD SD PD
FD I2 HD - Harmonic #15 STD TD SD PD
FE I3 HD - Harmonic #15 STD TD SD PD
FF I4 HD - Harmonic #15 STD TD SD PD
The action keys specify the instance number for an object to perform an action on.
The following action keys are possible:
Action Key
Setpoint
Supported
Meaning
0 - No action
1000-1004 STD HS Clear digital input counter 0-3 (Status input counter 1-4), 4=ALL
1100-1102 STD HS Operate Relay #1 to 3
1C00-1C04 STD HS same as 1000-1004
A400-A407 STD HS Waveform Capture channels #1 to 8
A500 STD HS Waveform Recorder
Action keys marked with STD are supported by Standard Setpoints (1–11), action
keys marked with HS are supported by High Speed Setpoints (1–6).
Page view 217
1 2 ... 213 214 215 216 217 218 219 220

Comments to this Manuals

No comments