GE General Electric Computer Accessories Medium Voltage GP Type G Drives User Manual Page 42

  • Download
  • Add to my manuals
  • Print
  • Page
    / 266
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 41
2-26
Chapter 2 Faults and Troubleshooting Innovation Series Medium Voltage GP Type - G Drives GEH-6385
No. Name Type Description
123 AS1 IGDM card flt Trip
The AS1 IGDM card flt trip fault is hardware generated. The trip fault occurs
when the bridge control has lost communication with the indicated IGDM
module. This communication occurs via fiber optic cable between the FOSA
and the IGDM. During normal operation the IGDM transmits continuous light
back to FOSA. Any loss of this signal triggers this trip fault.
Several unrelated situations can cause the light to stop transmitting. Run the
Cell Test Wizard to identify any failed devices.
Primary causes:
CPFP power supply failure
IGDM failure
A desat fault on the indicated IGBT was detected.
Possible board failures:
IGDM
CPFP
FOSA
BICM
Possible wiring faults:
Fiber optic connection between FOSA and IGDM
Power distribution wiring from CPFP.
124 AS2 IGDM card flt Trip The AS2 IGDM card flt trip fault is hardware generated. The trip fault occurs
when the bridge control has lost communication with the indicated IGDM
module. This communication occurs via fiber optic cable between the FOSA
and the IGDM. During normal operation the IGDM transmits continuous light
back to FOSA. Any loss of this signal triggers this trip fault.
Several unrelated situations can cause the light to stop transmitting. Run the
Cell Test Wizard to identify any failed devices.
Primary causes:
CPFP power supply failure
IGDM failure
A desat fault on the indicated IGBT was detected.
Possible board failures:
IGDM
CPFP
FOSA
BICM
Possible wiring faults:
Fiber optic connection between FOSA and IGDM
Power distribution wiring from CPFP.
Page view 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 265 266

Comments to this Manuals