AZ65H09DAC
GE Zoneline
®
Heat Pump Unit with Corrosion Protection, 230/208 Volt
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
For more information, please visit our website at zoneline.com or call 888.231.2548.
Specification Revised 7/16
ELECTRICAL WIRING
All wiring, including installation of receptacle, must
be made in accordance with local electrical codes
and regulations.
NOTE: Aluminum wiring may pose special problems –
consult a qualified electrician.
GRILLE OPTIONS
Stamped Aluminum Grille – RAG60
Exterior Architectural Louvers Durable Polycarbonate:
RAG61 (Beige) RAG63 (Dark Brown)
RAG62 (Maple)
Extruded Aluminum Architectural Grille – RAG67
RETROFIT KITS:
RAK40 – Deflector Kit to adapt chassis for use with
existing (non-GE) exterior louvered grilles.
DUCTED APPLICATIONS
AZ45 and AZ65 Series can be used with ductwork to heat
or cool more than one room. RAK6053 Duct Adaptor is
applied to the top of case over the air discharge. RAK601B
Duct Extension is applied to right or left of adaptor.
Locally fabricated ductwork may be added to extend to
maximum recommended straight distance of
15 feet in one direction.
ELECTRICAL CONNECTION
230/208 volt units may be plugged into a receptacle.
See Architects and Engineers Design Data Manual for
electrical connection information including use of sub-base
for direct connected units. Installation must comply with
local electrical codes and regulations.
Power connection kits are required on all Zoneline chassis.
MAXIMUM CORD EXTENSION
SIDE
VIEW
Inside
Room
Cabinet
Outside
58
21
Grille
7-1/8
RAB71A = 16
RAB77A = 16-1/4
RAB71A = 20-7/8
RAB77A = 21
Room Air/Installation QSart
A
C
B
Zoneline RAC Wall Installation
WALL CASE DIMENSIONS
RAB71B WALL SLEEVE
Heavy-gauge galvanized steel, with
insulation.
A – 42", B – 13-3/4", C – 16"
Also available in 16" and 24" depths
RAB77B WALL SLEEVE
Molded SMC fiberglass-reinforced
polyester compound.
A – 42-1/8", B– 13-7/8", C – 16-1/4"
WALL OPENING DIMENSIONS
Add 1/4" to A and C dimensions
for all cut-outs.
RAB71B 16-1/4" Min. H x 42-1/4" Min. W
RAB77B 16-1/2" Min. H x 42-3/8" Min. W
AZ45/65 HEATER KW
230/208
VOLT
LINE CORD (P), DIRECT (D) AND SUB-BASE CONNECTED UNITS
7K/9K 12K/15K
Power
Connection Kit
RAK315P
RAK315D
RAK204D15C
RAK320P
RAK320D
RAK204D20C
RAK330P
RAK330D
RAK204D30C
RAK315P
RAK315D
RAK204D15C
RAK320P
RAK320D
RAK204D20C
RAK330P
RAK330D
RAK204D30C
Total Watts 2410/1990 3420/2830 4830/3990 2430/2020 3450/2860 4860/4020
Heater Watts 2400/1960 3400/2780 4800/3930 2400/1960 3400/2780 4800/3930
Heater BTU 8100/6600 11600/9400 16300/13400 8100/6600 11600/9400 16300/13400
Total Amps 10.5/9.6 14.9/13.6 21.0/19.2 10.6/9.7 15.1/13.8 21.2/19.3
Min Circuit 15 20 30 15 20 30
Recommended
Protective
Device
15 amp time-
delay fuse or
breaker
20 amp time-
delay fuse or
breaker
30 amp time-
delay fuse or
breaker
15 amp time-
delay fuse or
breaker
20 amp time-
delay fuse or
breaker
30 amp time-
delay fuse or
breaker