GE Consumer & Industrial Power Protection Operating Manual Uninterruptible Power supply Digital Energy™ LP 33 Series 50 & 60 kVA 20
Modifications reserved Page 10/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3 DESCRIPTION 3.1 BLOCK DIAGRAM A
Modifications reserved Page 11/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3.2 OPERATION MODES This section d
Modifications reserved Page 12/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Automatic bypass operation In VFI
Modifications reserved Page 13/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Manual bypass operation The manual
Modifications reserved Page 14/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3.3 RPA PARALLEL SYSTEM The RPA
Modifications reserved Page 15/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3.4 UPS PARALLELED ON THE SAME BAT
Modifications reserved Page 16/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3.5 SERVICE AND TECHNICAL SUPPORT
Modifications reserved Page 17/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3.6 RECYCLING AT THE END OF SERVIC
Modifications reserved Page 18/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 4 LAYOUT 4.1 LAYOUT LP 33 Series /
Modifications reserved Page 19/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 5 SYSTEM HANDLING 5.1 CONTROL PANE
Modifications reserved Page 2/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Model: LP 33 Series / 50 & 60
Modifications reserved Page 20/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 5.2 COMMAND PUSH BUTTONS AND SWITC
Modifications reserved Page 21/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6 LCD SCREEN Shows the UPS system
Modifications reserved Page 22/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA MAINS f=60.0Hz U1=120V U2=119V U
Modifications reserved Page 23/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6.2 EVENT SCREENS (Alarm) Each of
Modifications reserved Page 24/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Code Alarm Meaning 4118 BATTERY
Modifications reserved Page 25/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Code Alarm Meaning 4520 NO INVER
Modifications reserved Page 26/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6.2.2 Messages list Are defined me
Modifications reserved Page 27/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Code Message Meaning 4362 INVERT
Modifications reserved Page 28/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Code Message Meaning 4602 Q1 OPE
Modifications reserved Page 29/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6.2.3 Event report LP 33 Series In
Modifications reserved Page 3/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Dear Customer, We thank you for se
Modifications reserved Page 30/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6.3 MENU SCREENS (Menu) Pressing
Modifications reserved Page 31/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6.3.1 User parameters screen This
Modifications reserved Page 32/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3. Telephone numbers set-up Tel1:
Modifications reserved Page 33/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 2. d1 ÷ d7: Enabling time in func
Modifications reserved Page 34/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Example 4: If the ECO Mode must be
Modifications reserved Page 35/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7 OPERATION 7.1 PROCEDURES FOR S
Modifications reserved Page 36/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3. Switch On the output switch Q1
Modifications reserved Page 37/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.1.2 UPS shutdown with load trans
Modifications reserved Page 38/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6. In order to discharge the DC li
Modifications reserved Page 39/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.1.3 Start-up following the opera
Modifications reserved Page 4/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Preface Congratulations on your ch
Modifications reserved Page 40/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.1.4 Complete shutdown As a resul
Modifications reserved Page 41/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.1.5 Restore to normal operation
Modifications reserved Page 42/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.1.6 Restore to normal operation
Modifications reserved Page 43/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2 PROCEDURES FOR PARALLEL SYSTE
Modifications reserved Page 44/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 3. Switch ON the output switch Q1
Modifications reserved Page 45/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.2 Parallel UPS shutdown with l
Modifications reserved Page 46/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 6. In order to discharge the DC li
Modifications reserved Page 47/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.3 Start-up following the opera
Modifications reserved Page 48/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.4 Shutdown of a single unit in
Modifications reserved Page 49/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.5 Start-up an additional unit
Modifications reserved Page 5/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Table of contents Page 1 SAFETY R
Modifications reserved Page 50/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.6 Complete shutdown of a paral
Modifications reserved Page 51/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.7 Restore to normal operation
Modifications reserved Page 52/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 7.2.8 Restore to normal operation
Modifications reserved Page 53/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 8 OPTIONS 8.1 OPTIONS GENERAL VI
Modifications reserved Page 54/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 9 MAINTENANCE WARNING ! All maint
Modifications reserved Page 55/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 9.4 SERVICE REQUIRED LP 33
Modifications reserved Page 56/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 10 NOTES 10.1 NOTES FORM It is
Modifications reserved Page 57/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA RIDER FOR WARRANTY FOR SALE OF Site
Modifications reserved Page 6/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 1 SAFETY RULES With this document
Modifications reserved Page 7/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA SAVE THESE INSTRUCTIONS This manual
Modifications reserved Page 8/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA Safety symbols and warnings Safety
Modifications reserved Page 9/57 OPM_LPS_3UO_50K_60K_0US_V010.doc Operating Manual LP 33 Series 50 & 60 kVA 2 INTRODUCTION 2.1 GENERAL DESCRIP