GE General Electric Electronic Accessory ge multilin User Manual

Browse online or download User Manual for Networking GE General Electric Electronic Accessory ge multilin. GE General Electric Electronic Accessory ge multilin User's Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - GE MULTILIN

GE MULTILIN TM PMCS 6.15 Read-This-Book-First Installation Guide DEH-211 GE Power Management Control System

Page 2

Introduction Welcome Hello and welcome to the POWER LEADER Power Management Control System for CIMPLICITY® HMI. You are about to begin using your comp

Page 3

About CIMPLICITY PMCS Version 6.15 CIMPLICITY PMCS Version 6.15 is the latest Power Management Control System in the robust line of POWER LEADER powe

Page 4

• CIMPLICITY PMCS Interface Toolkit with tools to quickly create accurate, intelligent floor plans, one-line diagrams, and elevation views. • System

Page 5

(This page left blank intentionally) CIMPLICITY PMCS Read-This-Book-First Introduction • 9

Page 6 - Contents

Getting Started First Steps If you are already familiar with PMCS, simply review the system requirements and skip ahead to Chapter 3. Getting started

Page 7

Communication network: A physical standard for wiring and interconnection of communicating devices. A communication network standard usually includes

Page 8

NetDDE: A version of Dynamic Data Exchange (DDE) that allows communications between applications running on different PCs over network connections. NT

Page 9

System Requirements The following table shows the minimum and recommended PC system configuration for running PMCS Version 6.15. Note that regardles

Page 10 - Introduction

PMCS 6.15 Envelope definition 1) Physical System Size • 75 power management devices (IEDs) (100 max), • 150 I/O points (through IEDs or PLC

Page 11 - Features

Where to Get Help The GE Industrial Systems Resolution Center is available at 1-888-GE-RESOLV to answer your questions about installing or using PMC

Page 12 - Supported Devices

Notice The information contained in this document is subject to change without notice. GE makes no warranty of any kind with regard to this material,

Page 13

(This page left blank intentionally) 16 • Getting Started CIMPLICITY PMCS Read-This-Book-First

Page 14 - Getting Started

Installing the Software Computer Preparation PMCS must be installed on a PC running Windows 2000 SP4. This host PC must be dedicated to the PMCS syst

Page 15

When Installing On Windows 2003 Server The Following steps to be executed before starting the PMCS installation. This applies for all the licenses of

Page 16

Click on Apply and then click on Ok button. After this restart the PC and then start the PMCS installation process as mentioned in this document. In

Page 17 - System Requirements

Installing Additional Software Install any additional software, such as Microsoft Excel, at this point in the procedure. Follow the instruction proced

Page 18 - 2) HMI Application Size

Select the appropriate network adapter from the list and click Have Disk…. Follow the instructions provided on the screen to complete the network ca

Page 19 - What’s next?

Local Area Network (LAN) Interfaces PMCS supports multiple View Nodes through NetDDE links over a local area network. Thus, in addition to the PMCS n

Page 20

Installing Additional Software Install any additional software, such as Microsoft Excel or COMTRADE file browsers for analyzing waveform files, at th

Page 21 - Installing the Software

your eLicense Option screen (see below). This screen allows you to either trial or fully license your PMCS software. 720 Hours (30-Day) Trial

Page 22

Selecting the Web License option from the License Option brings you to the Web License Screen. This screen requires you to enter your eLicense Order

Page 23 - Installing CIMPLICITY

GE MULTILIN TM PMCS 6.15 Read-This-Book-First Microsoft, Microsoft Excel and Microsoft PowerPoint are registered trademarks, and Windows 2000 is a

Page 24

2. When the system on which PMCS is being installed is not having any .Net Framework installed on it. The PMCS 6.15 installation will go ahead by ins

Page 25

3. In the Run dialog box, enter X:\setup (where X is the appropriate CD-ROM drive designation). 4. The below screen is observed when .Net is not

Page 26

28 • Installing the Software CIMPLICITY PMCS Read-This-Book-First

Page 27 - Installing the PMCS software

5. Click on I agree and click on Install button. It will now install .Net Framework on the machine where PMCS installation is started. After the .

Page 28 - Licensing via the Web

6. GE PMCS 6.15 welcome screen appears. When you select the Next button in the Welcome screen, the PMCS license agreement screen is shown. Please t

Page 29 - PMCS Installation Steps

7. At the User Information screen shown below, enter your name, your company name, and the serial number for the PMCS component you are installing

Page 30

When you select the Next button in the User Information screen, a registration confirmation screen prompts you to verify your entries. Ensure that y

Page 31

At the Choose Destination Location dialog, specify a drive on which to install PMCS. Default is “C”. Click Next to continue. CIMPLICITY PMCS Read-Th

Page 32

9. At the Setup Type screen, select Custom installation, standard PMCS installation, or PMCS with EPM 7700 Components. PMCS installation is recommend

Page 33

10. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9), skip this step and proceed to Step 13. If you are i

Page 35

11. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9) or if you selected “Primary Node Installation” in Ste

Page 36

12. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9), or if you selected “Primary Node Installation” in S

Page 37

13. Select the Program Folder for PMCS installation. It is recommended that the default Program Folder be chosen. Click Next to continue. 38 • Ins

Page 38

14. If you chose the “PMCS” installation, you may be presented with one DDE Server selections depending upon the PMCS catalog number you entered in

Page 39

40 • Installing the Software CIMPLICITY PMCS Read-This-Book-First

Page 40

16. The Selected Components screen offers you the opportunity to verify the installation settings before any files are copied to your hard drive. C

Page 41

17. After completing the selected PMCS installation, the installation program checks the host PC for an older version of the POWER LEADER Modbus Moni

Page 42

If No is selected and clicked on finish it will prompt the below message box and will again redirect to the above dialog asking to restart. So sele

Page 43

. After PMCS IIS – Setting up PMCS Server For any PMCS remote viewer system to connect to the PMCS server, the prerequisite is to have IIS installed

Page 44

In order to unlicense your software to use your eLicense Order ID for another computer – you must have an internet connection. To retrieve your licen

Page 45

(This Page is Left Blank Intentionally) CIMPLICITY PMCS Read-This-Book-First • i

Page 46

NOTE: The Uninstaller may not delete some files such as error logs, system logs, and configuration records, which are created after the PMCS installat

Page 47

Reinstallation Steps Follow the procedure below to reinstall your PMCS software. 1. If your system includes the PMCS Interface Toolkit, uninstall th

Page 48 - Un-elicensing PMCS

Upgrading from previous versions to PMCS 6.15 PMCS 6.15 provides an easy-to-use, automatic upgrade path from previous versions of PMCS. The software

Page 49 - Uninstalling PMCS

WARNING: Event Logger users only: Upgrading your EventServer or Eventlogger application will result in the loss of all device configurations and ann

Page 50

Working with Cimplicity Viewer Node How to view the screens on a viewer node To configure the project on a Cimplicity viewer node, running on a

Page 51 - Reinstallation Steps

CIMPLICITY PMCS Read-This-Book-First • 51

Page 52

Configuring the Software To get the most out of your new PMCS system, follow the directions below to configure your system. Organize Your Informati

Page 53

Ethernet Gateway IP Address COM port Modbus RTU Address Device Type Device (Topic) Name 10.47.28.201 1 2 EPM 9650Q E9650Q 10.47.28.201 1 12 E3720

Page 54

Configuration Procedure Follow the procedure below to efficiently configure your system and minimize your time to startup. Host PC Configuration 1. C

Page 55

EPM Software Components Configuration The EPM 7700, EPM 7600 and EPM 7500 requires several separate software components which are installed during th

Page 56 - Configuring the Software

Back to Main Page Contents Introduction 6 Welcome...

Page 57 - View Node

(This page left blank intentionally) 56 • Configuring the Software CIMPLICITY PMCS Read-This-Book-First

Page 58 - Configuration Procedure

EPM Device-Special Considerations Introduction The GE EPM 7700, EPM 7600 and EPM 7500 devices add new level of power management capabilities to PMCS.

Page 59

EPM Software Components There are four major components of the EPM software. The Network Builder, ION Designer, Communications Server, and ION_LINK DD

Page 60

Workstation Configuration Guidelines If you are using the EPM 7700, EPM 7600 or EPM 7500 Meters in your PMCS network, the following guidelines in thi

Page 61 - Special Considerations

Configuring the EPM Device Network The PMCS installation routine described earlier in this manual creates initial workstation and software node entri

Page 62 - EPM Software Components

Building the Power-Monitoring Network in NetBuilder When Network Builder is running, you can begin configuring your EPM system by adding a site to th

Page 63

Adding Software Nodes Software nodes identify the various software components in the network. Stationless Secondary nodes, although they are physicall

Page 64 - Running Network Builder

Adding an Ethernet Site An Ethernet site defines the network connection between the devices and the Workstation(s). You add Ethernet sites to Worksta

Page 65 - NetBuilder

Set the following communications parameters for the site. • Enter the Transmit delay setting (in milliseconds). This setting determines the level o

Page 66 - Adding Software Nodes

Adding Devices (Meters) To add a meter, right-click on the Ethernet site you want to add the meter to, and select Insert Device… from the pop-up menu

Page 67 - Adding an Ethernet Site

Organize Your Information...52 Configuration Procedure ...

Page 68

(This page left blank intentionally) 66 • EPM Device-Special Considerations CIMPLICITY PMCS Read-This-Book-First

Page 69 - Saving and Exiting

Index A alarm, 4 D DDE Server, 54 E Ethernet, 4, 8, 18, 19, 48, 50 event, 4 F Fanuc, 4 First Steps, 7 I Interface Toolkit, 5, 8, 43, 50 M minimum sys

Page 70

GE MULTILIN General Electric Company 215 Anderson Avenue, Markham ON, L6E 1B3,

Page 72 - GE MULTILIN

(This page left blank intentionally) CIMPLICITY PMCS Read-This-Book-First Introduction • 5