GEH-5833
INSTRUCTIONS
Decashield
®
175 Luminaire
READ THOROUGHLY BEFORE INSTALLING
GENERAL
This luminaire is designed for outdoor lighting applica-
tions, and should not be used in areas of limited ventila-
tion, or in high ambient temperature enclosures; it should
be installed and maintained according to following recom-
mendations.
UNPACKING
This luminaire has been properly packed so that no parts
should have been damaged during transit. Inspect to
confirm.
INSTALLATION
WIRING:
Make all electrical connections in accordance with
the National Electrical Code and any applicable
local code requirements.
Verify that supply voltage is correct by comparing it
to nameplate.
If unit is designated as multivolt or multiwatt,
follow specific instruction.
Do not remove insulated connectors from wires not
needed for required voltage connection.
Pigtail leads are provided for supply connection. System
neutral should be connected to the white lead. Green lead
is equipment ground.
SINGLE VOLTAGE UNITS: Are completely wired so
that the user needs to connect only the supply conductors
to the primary leads and the fixture ground.
MULTIVOLT UNITS:
a) Internally Reconnectable Multi-Volts: If no line voltage is
specified on the nameplate, or if a voltage other than the
one specified is required, refer to Figure 1 and open the
luminaire and gain access to the ballast. Make the
desired voltage selection as outlined in the instruction
tag attached to the black lead with the insulated
terminal. Be careful to move only the one lead having
the insulated terminal; then proceed with the installa-
tion.
b) Externally Reconnectable Multi-Volts: (120 or 277
volts) Follow the connection diagram on the wiring
label attached to the luminaire for proper wiring.
Figure 1
WARNING
Risk of electric shock
Turn power off before servicing
see instructions
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or
maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to GE Lighting Solutions.
g
GE
Lighting Solutions
Page view 0
1 2 3 4

Summary of Contents

Page 1 - 175 Luminaire

GEH-5833INSTRUCTIONSDecashield® 175 LuminaireREAD THOROUGHLY BEFORE INSTALLINGGENERALThis luminaire is designed for outdoor lighting applica-tions, an

Page 2 - LAMP INSTALLATION/REPLACEMENT

MOUNTING FINAL ASSEMBLYPHOTOELECTRIC CONTROLThe photoelectric control receptacle (if present) shouldbe oriented before the control is installed. Loose

Page 3 - Luminaire Decashield

GEH-5833INSTRUCTIONSLuminaire Decashield ® 175À LIRE TOTALEMENT AVANT D'INSTALLERPRÉSENTATIONCe luminaire est conçu pour fournir un éclairage à l

Page 4 - ATTENTION

MONTAGE35-201578-7K(12/00)ASSEMBLAGE FINALCOMMANDE PHOTOÉLECTRIQUELe réceptacle de la commande photoélectrique (si elle est installée)doit être orient