GE 15136 Instruction Manual

Browse online or download Instruction Manual for Electrical timers GE 15136. GE 15136 Instructions / Assembly User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SPECIFICATIONS
Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based
upon dipswitch configuration.
Switch Rating: DPDT Models
Normally Open Contacts
40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac ;
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
5.4A Tungsten, 208-277Vac.
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240-277Vac.
TV-5, 120Vac
Normally Closed Contacts
30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.
NOTE: If loads are connected to both NC and NO contacts, both contacts are
derated to 67% of the above values.
ENVIRONMENTAL RATINGS
Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing
WIRING CONNECTIONS
Screw clamp terminals for up to 2, 8 AWG wires per position. For supply
connections, use 8AWG or larger wires suitable for at least 105° C. Use copper
conductors only.
Lights
Power LED (Orange) – Light illuminates when power is applied to
the timer
Status LED (Green) – Light illuminates when power is applied to load.
INSTALLATION
CAUTION: Before wiring or service, power to this time switch and the
equipment it controls must be turned off. Turning off the timer switch only
will not prevent a shock hazard. Replace cover plate within housing before
supplying power to time switch. Installation should be performed by a
licensed electrician only. Before installing this product read all instructions
carefully. Remove protective cover panel within time switch housing by
removing screws located below timer face.
Dipswitch Configuration
WARNING: Failure to properly configure the dipswitch will result in
damage to the unit and void the warranty! Before installing and wiring the GE
Time Switch, proper configuration must be selected. This is accomplished as
follows:
120VAC 277VAC (Default)208~240VAC
ON OFF ON OFFON OFF
ALL ON ALL OFF1 & 4 OFF
2 & 3 ON
Digital Time Switch
NOTE: For outdoor locations, rain tight or wet location conduit hubs that
comply with requirements of UL 514B (standard for fittings for conduit and
outlet boxes) must be used.
1. To mount the box, remove the timer mechanism. Push the latch at the
top of the timer mechanism. The mechanism will release and pull out of
box.
2. Select knockouts to be used. Remove the inner 1/2” knockout by
inserting a screwdriver in the slot and carefully punch knockout loose.
Remove slug. If the 3/4” knockout is required, remove the outer ring
with pliers after removing the 1/2” knockout. Smooth edges with file if
necessary.
3. Place enclosure in desired mounting location and mark the three
mounting holes.
4. Drill holes for #8 screws using 1/8” drill bit, start screws in holes.
5. Place enclosure over screws and tighten screws.
6. Connect conduit hubs to conduit before connecting the hubs to the
enclosure. After inserting hubs into enclosure, carefully tighten hub lock
nut. Do not over-tighten.
7. Install in accordance with all applicable National and Local code
requirements. See Figure 1 and wiring diagrams.
8. To place the timer mechanism back in the metal box timer first hold top
of the timer mechanism. Slide the plastic case into the metal box latches
in the center of the metal box. Push the top of the timer mechanism until
the metal latch snaps into place.
GROUNDING: This enclosure has a grounding block on the bottom/
inside of the timer box. Screw in all ground wires to the ground block.
A pool application does not require bonding.
This enclosure does not provide grounding between conduits. When using
non-metallic conduit or cable, connect the ground wires of all cables together
with a wire nut. When metallic conduit is used, use grounding type bushings
and a jumper wire between each conduit.
15136
Page view 0
1 2 3

Summary of Contents

Page 1 - Digital Time Switch

SPECIFICATIONSInput Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based upon dipswitch configuration.Switch Rating: DPDT ModelsNormally Open C

Page 2 - Basic Settings

TIMERN CN OCOMNC2NO2COM2LOADL1L2TIMERN CN OCOMTO 200/240/277V LINETO 120V LINENC2NO2COM2HNLOADTIMERN CN OCOMTO 24V LINENC2NO2COM2HNLOADNHTO 120V LINET

Page 3

Programming Countdown Operation:1. Press the “Timer” button replacing to scroll through the 9 ON/OFF settings to get to the ON C setting.2. Press th